Troubleshooting
26
Low temperature thermostat
We strongly suggest that you install one thermostat used for low temperature detection (around 46 F
or 8 C). Connect this thermostat in parallel with the heating relay or auxiliary heating relay. Therefore,
should CARDIO be defective, there will be another security device.
Only one sub-system does not work
(heating or cooling or fan)
1. check connections on terminal blocks;
2. check relays, wiring and breakers associated with these systems.
The touch screen does not show the right temperature
For various reasons, temperature readings at the screen may differ from temperature readings
elsewhere in the room. Use “compensation of the temperature” in the Temperature menu of the
Installer configuring menu.
Quick cycling of the temperature control system
This is due to the screens being to close to heating/cooling source.
1. give more inertia to CARDIO’s temperature control sensitivity by setting the right data in
“hysteresis” ( see p.13).
!WARNING!: read technical specifications of relays to be installed. CARDIO’s relays
only allow loads with the following characteristics:
Resistive: 24VAC
Inductive: 24VAC
If you use relays with higher than 24VAC, protection circuits will be damaged.